![ABB Relion REC615 Скачать руководство пользователя страница 495](http://html.mh-extra.com/html/abb/relion-rec615/relion-rec615_technical-manual_3045253495.webp)
5.3.6.2
TRPPTRC Output signals
Table 527: TRPPTRC Output signals
Name
Type
Description
TRIP
BOOLEAN
General trip output signal
CL_LKOUT
BOOLEAN
Circuit breaker lockout out-
put (set until reset)
5.3.7
Settings
5.3.7.1
TRPPTRC Non group settings (Basic)
Table 528: TRPPTRC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Trip pulse time
20...60000
ms
1
250
Minimum duration
of trip output sig-
nal
Trip output mode
1=Non-latched
2=Latched
3=Lockout
1=Non-latched
Select the opera-
tion mode for trip
output
5.3.8
Monitored data
5.3.8.1
TRPPTRC Monitored data
Table 529: TRPPTRC Monitored data
Name
Type
Values (Range)
Unit
Description
TRPPTRC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
1MRS758755 C
Protection related functions
REC615 & RER615
Technical Manual
495