![ABB Relion REC615 Скачать руководство пользователя страница 494](http://html.mh-extra.com/html/abb/relion-rec615/relion-rec615_technical-manual_3045253494.webp)
OR
TRIP
CL_LKOUT
BLOCK
RST_LKOUT
TRPPTRC1
OPERATE
NSPTOC2_OPERATE
FPHLPDOC1_OPERATE
PHHPTOC1_OPERATE
PHIPTOC1_OPERATE
FDPHLPDOC1_OPERATE
DPHHPDOC1_OPERATE
EFPADM1_OPERATE
EFPADM2_OPERATE
EFPADM3_OPERATE
WPWDE1_OPERATE
WPWDE2_OPERATE
FDPHLPDOC2_OPERATE
X100 PO1
PDNSPTOC1_OPERATE
WPWDE3_OPERATE
NSPTOC1_OPERATE
ROVPTOV1_OPERATE
ROVPTOV2_OPERATE
PHPTOV1_OPERATE
PHPTOV2_OPERATE
PHPTOV3_OPERATE
PHPTUV1_OPERATE
PHPTUV2_OPERATE
PHPTUV3_OPERATE
NSPTOV1_OPERATE
PSPTUV1_OPERATE
SPCGGIO1_SW_MODE_ENA
FEFLPTOC1_OPERATE
EFIPTOC1_OPERATE
EFHPTOC1_OPERATE
FDEFLPDEF1_OPERATE
DEFHPDEF1_OPERATE
FDEFLPDEF2_OPERATE
FRPFRQ2_OPERATE
FRPFRQ1_OPERATE
Figure 246: Typical TRPPTRC connection with RER615
5.3.6
Signals
5.3.6.1
TRPPTRC Input signals
Table 526: TRPPTRC Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0=False
Block of function
OPERATE
BOOLEAN
0=False
Operate
RST_LKOUT
BOOLEAN
0=False
Input for resetting
the circuit breaker
lockout function
Protection related functions
1MRS758755 C
494
REC615 & RER615
Technical Manual
Содержание Relion REC615
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......