3.1.12
HMI settings
Table 19: HMI settings
Parameter
Values (Range)
Unit
Step
Default
Description
FB naming conven-
tion
1=IEC61850
2=IEC60617
3=IEC-ANSI
1=IEC61850
FB naming conven-
tion used in IED
Default view
1=Measurements
2=Main menu
3=SLD
1=Measurements
LHMI default view
Backlight timeout
1...60
min
1
3
LHMI backlight
timeout
Web HMI mode
1=Active read only
2=Active
3=Disabled
3=Disabled
Web HMI function-
ality
Web HMI timeout
1...60
min
1
3
Web HMI login
timeout
SLD symbol format 1=IEC
2=ANSI
1=IEC
Single Line Dia-
gram symbol for-
mat
Autoscroll delay
0...30
s
1
0
Autoscroll delay
for Measurements
view
Setting visibility
1=Basic
2=Advanced
1=Basic
Setting visibility for
HMI
3.1.13
IEC 60870-5-101/104 settings
Table 20: IEC 60870-5-101/104 settings
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on 5=off
5=off
Selects if this protocol instance is ena-
bled or disabled
Port
1=IEC101 - COM 1
2=IEC101 - COM 2
3=IEC104 - Ethernet
3=IEC104 -
Ethernet
Port selection
ClientIP
0.0.0.0
IP address of the client
TCP Port
0...65535
1
2404
Server TCP port
Start Delay
0...20
char
1
4
Frame start delay for serial communica-
tion
End Delay
0...20
char
1
4
Frame end delay for serial communication
Device Address
1...65535
1
1
Device address
ASDU Address
1...65535
1
1
Common address of ASDU
Link Mode
0=Balanced
1=Unbalanced
0=Balanced
Link mode setting
Table continues on the next page