3.1.5
Authorization settings
Table 11: Authorization settings
Parameter
Values (Range)
Unit
Step
Default
Description
Remote Update
0=Disable
1=Enable
0=Disable
Remote update
Secure Communi-
cation
0=False
1=True
1=True
Secure Communi-
cation
Authority logging
1=None
2=Configuration
change
3=Setting group
4=Setting group,
control
5=Settings edit
6=All
1=None
Authority logging
level
Remote override
0=False
1
1=True
2
1=True
Disable authority
Remote viewer
0
Set password
Remote operator
0
Set password
Remote engineer
0
Set password
Remote adminis-
trator
0
Set password
Local override
0=False
3
1=True
4
1=True
Disable authority
Local viewer
0
Set password
Local operator
0
Set password
Local engineer
0
Set password
Local administrator
0
Set password
1
Authorization override is disabled, communication tools ask password to enter the protection
relay.
2
Authorization override is enabled, communication tools do not need password to enter the
protection relay, except for WHMI which always requires it.
3
Authorization override is disabled, LHMI password must be entered.
4
Authorization override is enabled, LHMI password is not asked.
1MRS758755 C
Basic functions
REC615 & RER615
Technical Manual
45