3.1.2
Analog input settings, residual current
Table 8: Analog input settings, residual current
Parameter
Values (Range)
Unit
Step
Default
Description
Primary current
1.0...6000.0
A
0.1
100.0
Primary current
Secondary current
1=0.2A
2=1A
3=5A
2=1A
Secondary current
Amplitude Corr
0.9000...1.1000
0.0001
1.0000
Amplitude correc-
tion
Reverse polarity
0=False
1=True
0=False
Reverse the polari-
ty of the residual
CT
Angle correction
-20.0000...20.0000
deg
0.0001
0.0000
Angle correction
factor
3.1.3
Analog input settings, phase voltages
Table 9: nalog input settings, phase voltages
Parameter
Values (Range)
Unit
Step
Default
Description
Primary voltage 0.100...440.000
kV
0.001
11.547
Primary voltage
Secondary volt-
age
60...210
V
1
100
Secondary voltage
Amplitude Corr
0.9000...1.1000
0.0001
1.0000
Amplitude correc-
tion
Angle correction -20.0000...20.000
0
deg
0.0001
0.0000
Angle correction
factor
3.1.4
Analog input settings, residual voltage
Table 10: Analog input settings, residual voltage
Parameter
Values (Range)
Unit
Step
Default
Description
Primary voltage
0.100...440.000
1
kV
0.001
20.000
Primary rated voltage
Secondary voltage 60...210
V
1
100
Secondary rated voltage
VT connection
1=Wye
2=Delta
3=U12
4=UL1
2=Delta
Voltage transducer measurement
connection
Table continues on the next page
1
In 9-2 applications, Primary voltage maximum is limited to 126 kV.
1MRS758755 C
Basic functions
REC615 & RER615
Technical Manual
43