3
Basic functions
3.1
General parameters
3.1.1
Analog input settings, phase currents
Table 7: Analog input settings, phase currents
Parameter
Values (Range)
Unit
Step
Default
Description
Primary current
1.0...6000.0
A
0.1
100.0
Rated primary cur-
rent
Secondary current
2=1A
3=5A
2=1A
Rated secondary
current
Amplitude Corr A
0.9000 ... 1.1000
0.0001
1.0000
Phase A amplitude
correction factor
Amplitude Corr B
0.9000 ... 1.1000
0.0001
1.0000
Phase B amplitude
correction factor
Amplitude Corr C
0.9000 ... 1.1000
0.0001
1.0000
Phase C amplitude
correction factor
Nominal current
39...4000
A
1
1300
Network Nominal
Current (In)
Rated secondary
Val
1.000...150.000
mV/Hz
0.001
3.000
Rated Secondary
Value (RSV) ratio
Reverse polarity
0=False
1=True
0=False
Reverse the polari-
ty of the phase CTs
Angle Corr A
-20.0000...20.0000
deg
0.0001
0.0000
Phase A angle cor-
rection factor
Angle Corr B
-20.0000...20.0000
deg
0.0001
0.0000
Phase B angle cor-
rection factor
Angle Corr C
-20.0000...20.0000
deg
0.0001
0.0000
Phase C angle cor-
rection factor
Basic functions
1MRS758755 C
42
REC615 & RER615
Technical Manual
Содержание Relion REC615
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...