EFPADM Monitored data
Table 385: EFPADM Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start
time / operate
time
FAULT_DIR
Enum
0=unknown
1=forward
2=backward
3=both
Detected fault
direction
COND_RES
FLOAT32
-1000.00...1000.0
0
mS
Real part of cal-
culated neutral
admittance
SUS_RES
FLOAT32
-1000.00...1000.0
0
mS
Imaginary part
of calculated
neutral admit-
tance
EFPADM
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.2.4.10
Technical data
Table 386: EFPADM Technical data
Characteristic
Value
Operation accuracy
1
At the frequency f = f
n
±1.0% or ±0.01 mS
(In range of 0.5...100 mS)
Start time
2
Minimum
Typical
Maximum
56 ms
60 ms
64 ms
Reset time
40 ms
Operate time accuracy
±1.0% of the set value of ±20 ms
Suppression of harmonics
-50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
4.2.5
Harmonics-based earth-fault protection HAEFPTOC
1
Uo = 1.0 × Un
2
Includes the delay of the signal output contact, results based on statistical distribution of 1000
measurements
1MRS758755 C
Protection functions
REC615 & RER615
Technical Manual
367