![ABB Relion REC615 Скачать руководство пользователя страница 125](http://html.mh-extra.com/html/abb/relion-rec615/relion-rec615_technical-manual_3045253125.webp)
3.15.8.3
Signals
Table 78: GOOSERCV_INT32 Output signals
Name
Type
Description
OUT
INT32
Output signal
VALID
BOOLEAN
Output signal
3.16
Type conversion function blocks
3.16.1
QTY_GOOD function block
3.16.1.1
Function block
Figure 55: Function block
3.16.1.2
Functionality
The QTY_GOOD function block evaluates the quality bits of the input signal and
passes it as a Boolean signal for the application.
The
IN
input can be connected to any logic application signal (logic function
output, binary input, application function output or received GOOSE signal). Due
to application logic quality bit propagation, each (simple and even combined) signal
has quality which can be evaluated.
The
OUT
output indicates quality good of the input signal. Input signals that have no
quality bits set or only test bit is set, will indicate quality good status.
3.16.1.3
Signals
Table 79: QTY_GOOD Input signals
Name
Type
Default
Description
IN
Any
0
Input signal
Table 80: QTY_GOOD Output signals
Name
Type
Description
OUT
BOOLEAN
Output signal
1MRS758755 C
Basic functions
REC615 & RER615
Technical Manual