Table 66: ULTVTR Output signals
Name
Type
Description
ALARM
BOOLEAN
Alarm
WARNING
BOOLEAN
Warning
3.14.3.5
Settings
Table 67: ULTVTR Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Primary voltage
0.100...440.000
kV
0.001
20.000
Primary rated voltage
Secondary voltage 60...210
V
1
100
Secondary rated voltage
VT connection
1=Wye
2=Delta
3=U12
4=UL1
2=Delta
Voltage transducer measure-
ment connection
Amplitude Corr A
0.9000 ... 1.1000
0.0001
1.0000
Phase A Voltage phasor magni-
tude correction of an external
voltage transformer
Amplitude Corr B
0.9000 ... 1.1000
0.0001
1.0000
Phase B Voltage phasor magni-
tude correction of an external
voltage transformer
Amplitude Corr C
0.9000 ... 1.1000
0.0001
1.0000
Phase C Voltage phasor magni-
tude correction of an external
voltage transformer
Division ratio
1000 ... 20000
1
10000
Voltage sensor division ratio
Voltage input type
1=Voltage trafo
3=CVD sensor
1=Voltage trafo Type of the voltage input
Angle Corr A
-20.0000...20.0000
deg
0.0001
0.0000
Phase A Voltage phasor angle
correction of an external volt-
age transformer
Angle Corr B
-20.0000...20.0000
deg
0.0001
0.0000
Phase B Voltage phasor angle
correction of an external volt-
age transformer
Angle Corr C
-20.0000...20.0000
deg
0.0001
0.0000
Phase C Voltage phasor angle
correction of an external volt-
age transformer
3.14.3.6
Monitored data
Monitored data is available in three locations.
• Monitoring > I/O status > Analog inputs
• Monitoring > IED status > SMV traffic
• Monitoring > IED status > SMV accuracy
3.14.4
RESTVTR function block
1MRS758755 C
Basic functions
REC615 & RER615
Technical Manual
117