IEC 61850-9-2 LE sampled values receiving SMVRCV
3.14.2.1
Function block
Figure 44: Function block
3.14.2.2
Functionality
The SMVRCV function block is used for activating the SMV receiving functionality.
3.14.2.3
Signals
Table 64: SMVRCV Output signals
Name
Type
Description
UL1
INT32-UL1
IEC61850-9-2 phase 1 voltage
UL2
INT32-UL2
IEC61850-9-2 phase 2 voltage
UL3
INT32-UL3
IEC61850-9-2 phase 3 voltage
U0
INT32-Uo
IEC61850-9-2 residual voltage
3.14.3
ULTVTR function block
3.14.3.1
Function block
Figure 45: Function block
3.14.3.2
Functionality
The ULTVTR function is used in the receiver application to perform the supervision
for the sampled values and to connect the received analog phase voltage inputs to
the application. Synchronization accuracy, sampled value frame transfer delays and
missing frames are being supervised.