15. Technical data
General
Definitions
Reference value
The specified value of an influencing factor to which are referred the characteristics of the equipment
Nominal range
The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the
specified requirements
Operative range
The range of values of a given energizing quantity for which the equipment, under specified conditions, is able to perform its
intended functions according to the specified requirements
Energizing quantities, rated values and limits
Analog inputs
Table 5. TRM - Energizing quantities, rated values and limits for protection transformer modules
Quantity
Rated value
Nominal range
Current
I
r
= 1 or 5 A
(0.2-40) × I
r
Operative range
(0-100) x I
r
Permissive overload
4 × I
r
cont.
100 × I
r
for 1 s
*)
Burden
< 150 mVA at I
r
= 5 A
< 20 mVA at I
r
= 1 A
Frequency
f
r
= 50/60 Hz
± 5%
*)
max. 350 A for 1 s when COMBITEST test switch is included.
Table 6. OEM - Optical ethernet module
Quantity
Rated value
Number of channels
1 or 2
Standard
IEEE 802.3u 100BASE-FX
Type of fiber
62.5/125
m
m multimode fibre
Wave length
1300 nm
Optical connector
Type ST
Communication speed
Fast Ethernet 100 MB
Auxiliary DC voltage
Table 7. PSM - Power supply module
Quantity
Rated value
Nominal range
Auxiliary dc voltage, EL (input)
EL = (24 - 60) V
EL = (90 - 250) V
EL
±
20%
EL
±
20%
Power consumption
50 W typically
-
Auxiliary DC power in-rush
< 5 A during 0.1 s
-
Busbar protection REB670
1MRK505212-BEN E
Pre-configured
Product version: 1.2
30
ABB
Содержание RELION REB670
Страница 1: ...Relion 670 series Busbar protection REB670 Pre configured Product Guide...