Table 49:
General settings parameters for the Measurement function
Setting
Short description
Selected
value
Comment
Operation
Operation
Disabled/Enabled
Enabled
Function must be
Enabled
PowAmpFact
Magnitude factor to scale power
calculations
1.000
Typically no scaling is required
PowAngComp
Angle compensation for phase
shift between measured I & V
180.0
Typically no angle compensation is
required. However here the required
direction of P & Q measurement is
towards busbar (Not per IED internal
default direction). Therefore angle
compensation have to be used in
order to get measurements in aliment
with the required direction.
Mode
Selection of measured current
and voltage
L1L2
Only UL1L2 phase-to-phase voltage
is available
k
Low pass filter coefficient for
power measurement, V and I
0.00
Typically no additional filtering is
required
VGenZeroDb
Zero point clamping in % of
Vbase
25
Set minimum voltage level to 25%
IGenZeroDb
Zero point clamping in % of
Ibase
3
Set minimum current level to 3%
VBase (set in
Global base)
Base setting for voltage level in
kV
35.00
Set LV side rated phase-to-phase
voltage
IBase (set in
Global base)
Base setting for current level in
A
495
Set transformer LV winding rated
current
SBase (set in
Global base)
Base setting for power in MVA
31.5
Set based on rated power
Measurement function application for a generator
SEMOD54481-110 v8
Single line diagram for this application is given in figure
.
Section 14
1MRK 505 370-UUS A
Monitoring
438
Busbar protection REB670 2.2 ANSI
Application manual
Содержание RELION REB670
Страница 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 24: ...18 ...
Страница 40: ...34 ...
Страница 72: ...66 ...
Страница 102: ...96 ...
Страница 266: ...260 ...
Страница 272: ...266 ...
Страница 290: ...284 ...
Страница 432: ...426 ...
Страница 542: ...536 ...
Страница 552: ...546 ...
Страница 553: ...547 ...