5.2.4
Function settings
GUID-C80D559E-594D-4F7B-B61E-4EA6723B603C v1
Table 68: Definite time current function - settings
Text
Unit
Default
Min
Max
Step
ParSet 4..1
P1
(Select)
Delay
s
01.00
0.02
60.00
0.01
I-Setting
I
N
02.00
0.02
20.00
0.01
MaxMin
MAX (1ph)
(Select)
NrOfPhases
001
1
3
2
CurrentInp
CT/VT-Addr
0
BlockInp
BinaryAddr
Always off
Trip
SignalAddr
Start
SignalAddr
5.2.5
Parameters
GUID-5E0B8E0E-A13D-4155-AF07-BF8DC0D4B0DF v1
Table 69: Definite time current function - parameters
Signal
Description
ParSet 4..1
Parameter for determining in which set of parameters a particular function is
active.
Delay
Time between the function picking up and tripping.
I-Setting
Pick-up current setting.
Forbidden settings: >2.8 I
N
(when supplied from metering CT cores)
MaxMin
Defines operation as overcurrent or undercurrent or with inrush blocking.Settings:
•
MIN (3ph): Undercurrent. Three-phase functions detect the highest phase
current. Not permitted for single-phase functions.
•
MIN (1ph): Undercurrent. Three-phase functions detect the lowest phase
current.
•
MAX (3ph): Overcurrent. Three-phase functions detect the lowest phase
current. Not permitted for single-phase functions.
•
MAX (1ph): Overcurrent. Three-phase functions detect the highest phase
current.
•
MAX-Inrush: Blocks during inrush currents if one phase exceeds setting.
NrOfPhases
Defines whether single or three-phase measurement.
CurrentInp
Defines the CT input channel.
All current I/P's may be selected.
BlockInp
Input for blocking the function.
•
F: not blocked
•
T: blocked
•
xx: all binary inputs (or outputs of protection functions)
Trip
Tripping signal
Start
Pick-up signal
5.2.6
Configuration
GUID-AAEE593B-EAB3-4D4F-98C1-B0AE296307D5 v1
The following parameters have to be set:
Section 5
1MRK 505 406-UEN B
Bay protection functions
92
Bay protection functions REB500
Technical manual
© Copyright 2019 ABB. All rights reserved