Section 4
System settings
4.1
Voltage transformers for bay protection
GUID-C56299BD-E6CE-4FD3-A0C4-6040FFEAF8D0 v1
The HMI500 Settings/Voltage transformers/Overview tab opens a dialog with the list of all
voltage transformers in the single-line diagram with their labels, bay labels primary and
secondary rated voltages.
In the Details view, the description can be edited in the input field Markings. The ratio is
determined by the primary and secondary ratings entered in the Transformer ratio input field.
The VT input is a single winding, which is suitable for all the main VT secondary ratings, the
effective voltage being set via HMI500 to either 100 V or 200 V. Other voltages are
accommodated by appropriately setting the scaling factor.
This menu item appears only if voltage transformers have been fitted.
17000039-IEC19000402-1-en.vsdx
IEC19000402 V1 EN-US
Figure 1:
Settings/Voltage transformers
4.2
Star point setting for bay protection
GUID-E46BBD87-3168-4615-9034-73AC7E11B8E4 v1
If a REB500 bay unit includes bay protection functionality with 3-phase voltage
measurement, the mode of VT connection 3Phase_Star is mandatory.
Setting example for BP applications:
VT data:
UN primary =
220 kV / √3
UN secondary =
110 V / √3
Connection to REB500:
3 phases_star (mandatory connection)
1MRK 505 406-UEN B
Section 4
System settings
Bay protection functions REB500
23
Technical manual
© Copyright 2019 ABB. All rights reserved