5.9.3.4
Measurements
GUID-4F266B55-988B-4E45-9509-C1016AAD18DC v1
•
Neutral voltage (3U
0
)
•
Neutral current (3I
0
)
•
Real power component of neutral power (3U
0
× 3I
0
, not rotated)
•
Apparent power component of neutral power (3U
0
× 3I
0
, not rotated)
•
Fault direction (1 = forwards, -1 = backwards; this variable only applies when the binary
input CB closed is active)
5.9.4
Function settings
GUID-EFA80494-FF22-4492-B958-A730DBCE3E47 v1
Table 89: Directional sensitive EF protection for grounded system function - settings
Text
Unit
Default
Min
Max
Step
ParSet 4..1
P1
(Select)
VoltageInp
CT/VT-Addr
VT U1-U3
CurrentInp
CT/VT-Addr
CT I1-I3
CTneutral
Line side
(Select)
I-Setting
I
N
0.100
0.100
1.000
0.01
V-Setting
U
N
0.200
0.003
1.000
0.001
Angle
deg
60.0
-90.0
90.0
5
ComMode
Permissive
(Select)
SendMode
MeasBwd
(Select)
1 Channel
off
(Select)
Echo
off
(Select)
t
Basic
s
0.050
0.000
1.000
0.001
t
Wait
s
0.050
0.000
0.500
0.001
tTransBlk
s
0.100
0.000
0.500
0.001
Ext block
BinaryAddr
Always off
Receive
BinaryAddr
Always off
CB closed
BinaryAddr
Always off
VT Superv
BinaryAddr
Always off
Ext Start L1
BinaryAddr
Always off
Ext Start L2
BinaryAddr
Always off
Ext Start L3
BinaryAddr
Always off
ExtTrip 3P
BinaryAddr
Always off
ExtTrip
BinaryAddr
Always off
Trip
SignalAddr
Start
SignalAddr
MeasFwd
SignalAddr
MeasBwd
SignalAddr
Send
SignalAddr
Recve Inh.
SignalAddr
Section 5
1MRK 505 406-UEN B
Bay protection functions
158
Bay protection functions REB500
Technical manual
© Copyright 2019 ABB. All rights reserved