5.4.4
Function settings
GUID-06F853AD-FD0E-4322-8662-E2E4E857BA98 v1
Table 72: Directional overcurrent definite time function - settings
Text
Unit
Default
Min
Max
Step
ParSet4..1
P1
(Select)
CurrentInp
CT/VT-Addr
CT I1-I3
VoltageInp
CT/VT-Addr
VT U1-U3
I-Setting
IN
2.00
0.20
20.00
0.01
Angle
Deg
45
-180
+180
15
Delay
s
1.00
0.02
60.00
0.01
tWait
s
0.20
0.02
20.00
0.01
MemDirMode
Select
Trip
(Select)
MemDuration
s
2.00
0.20
60.00
0.01
Receive
BinaryAddr
Always on
Ext Block
BinaryAddr
Always off
Trip
SignalAddr
Start
SignalAddr
Start L1
SignalAddr
Start L2
SignalAddr
Start L3
SignalAddr
MeasFwd
SignalAddr
MeasBwd
SignalAddr
5.4.5
Parameters
GUID-99FB9719-852F-4D10-A8C8-3BC3F9811CE2 v1
Table 73: Directional overcurrent definite time function - parameters
Signal
Description
ParSet4..1
Parameter for determining in which set of parameters a particular function is
active.
CurrentInp
Defines the CT input channel. Only three-phase CTs can be set.
VoltageInp
Defines the VT input channel. Only three-phase VTs can be set.
I-Setting
Pick-up setting for tripping.
Angle
Characteristic angle.
Delay
Delay between pick-up and tripping.
tWait
Time allowed for the directional decision to be received from the opposite end
in a blocking scheme.
MemDirMode
Determines the response of the protection after the time set for memorizing
power direction:
•
trip
•
block
MemDuration
Time during which the power direction last determined remains valid.
Table continues on next page
Section 5
1MRK 505 406-UEN B
Bay protection functions
100
Bay protection functions REB500
Technical manual