PID-6519-OUTPUTSIGNALS v5
Table 205: PHPIOC (50) Output signals
Name
Type
Description
TRIP
BOOLEAN
Trip signal from any phase
TR_A
BOOLEAN
Trip signal from phase A
TR_B
BOOLEAN
Trip signal from phase B
TR_C
BOOLEAN
Trip signal from phase C
8.1.5
Settings
IP11434-1 v2
PID-6519-SETTINGS v5
Table 206: PHPIOC (50) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disabled/Enabled
OpModeSel
2 out of 3
1 out of 3
-
-
1 out of 3
Select operation mode (2 of 3 / 1 of 3)
Pickup
5 - 2500
%IB
1
200
Phase current pickup in % of IBase
Table 207: PHPIOC (50) Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
MultPU
0.5 - 5.0
-
0.1
1.0
Multiplier for operate current level
Table 208: PHPIOC (50) Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base Value
groups
Table 209: PHPIOC (50) Non group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
PU_MinEd2Set
5 - 2500
%IB
1
5
Minimum settable operate phase current
level in % of IBase, for 61850 Ed.2 settings
PU_MaxEd2Set
5 - 2500
%IB
1
2500
Maximum settable operate phase current
level in % of IBase, for 61850 Ed.2 settings
Section 8
1MRK 502 066-UUS B
Current protection
448
Technical manual
Содержание Relion 670 series
Страница 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 62: ...56 ...
Страница 182: ...176 ...
Страница 692: ...686 ...
Страница 726: ...720 ...
Страница 1014: ...1008 ...
Страница 1242: ...1236 ...
Страница 1362: ...1356 ...
Страница 1386: ...1380 ...
Страница 1422: ...1416 ...
Страница 1431: ...1425 ...