7.9.5
Settings
PID-6488-SETTINGS v2
Table 150: ZMFCPDIS (21) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Disable/Enable operation of the function
OperationSC
NoSeriesComp
SeriesComp
-
-
NoSeriesComp
Selection of series compensation
operation Off / On
RLdFwd
0.01 - 5000.00
Ohm/p
0.01
60.00
Resistance determining the load
impedance area - forward
RLdRvFactor
1 - 1000
%RLdF
w
1
100
Resistance factor determining the load
impedance area - reverse
XLd
0.01 - 10000.00
Ohm/p
0.01
400.00
Resistance determining the load
impedance area - forward
LdAngle
5 - 70
Deg
1
30
Angle determining the load impedance
area
CVTType
Any
Passive type
None (Magnetic)
-
-
Passive type
CVT selection determining the filtering of
the function
OpModePPZ1
Disabled
Quadrilateral
Mho
MhoOffset
-
-
Quadrilateral
Enabled/Disabled and characteristic
setting for Ph-Ph loops, zone 1
OpModePGZ1
Disabled
Quadrilateral
Mho
MhoOffset
-
-
Quadrilateral
Enabled/Disabled and characteristic
setting for Ph-G loops, zone 1
X1FwPPZ1
0.01 - 3000.00
Ohm/p
0.01
30.00
Positive seq. reactance reach, Ph-Ph, zone
1, forward dir.
R1FwPPZ1
0.00 - 1000.00
Ohm/p
0.01
5.00
Positive seq. resistive reach, Ph-Ph, zone 1,
forward dir.
X1RvPPZ1
0.01 - 3000.00
Ohm/p
0.01
30.00
Pos. seq. react. reach, Ph-Ph, zone 1,
reverse direction
X1FwPGZ1
0.01 - 3000.00
Ohm/p
0.01
30.00
Positive seq. reactance reach, Ph-G, zone 1,
forward dir.
R1FwPGZ1
0.00 - 1000.00
Ohm/p
0.01
5.00
Positive seq. resistive reach, Ph-G, zone 1,
forward dir.
X0FwPGZ1
0.01 - 9000.00
Ohm/p
0.01
100.00
Zero seq. reactance reach, Ph-G, zone 1,
forward direction
R0FwPGZ1
0.00 - 3000.00
Ohm/p
0.01
15.00
Zero seq. resistive reach, Ph-G, zone 1,
forward direction
X1RvPgZ1
0.01 - 3000.00
Ohm/p
0.01
30.00
Pos. seq. react. reach, Ph-G, zone 1, reverse
direction
RFPPZ1
0.01 - 9000.00
Ohm/l
0.01
30.00
Fault resistance reach, Ph-Ph, zone 1
RFPGZ1
0.01 - 9000.00
Ohm/l
0.01
100.00
Fault resistance reach, Ph-G, zone 1
tPPZ1
0.000 - 60.000
s
0.001
0.000
Time delay to trip, Phase-Phase, zone 1
tPGZ1
0.000 - 60.000
s
0.001
0.000
Time delay to trip, Ground-Earth, zone 1
Table continues on next page
1MRK 502 066-UUS B
Section 7
Impedance protection
333
Technical manual
Содержание Relion 670 series
Страница 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 62: ...56 ...
Страница 182: ...176 ...
Страница 692: ...686 ...
Страница 726: ...720 ...
Страница 1014: ...1008 ...
Страница 1242: ...1236 ...
Страница 1362: ...1356 ...
Страница 1386: ...1380 ...
Страница 1422: ...1416 ...
Страница 1431: ...1425 ...