18.4.2
Communication interfaces and protocols
GUID-35C845D3-574A-40D1-AEF1-9E0D330E31DE v6
Table 809: Supported station communication interfaces and protocols
Protocol
Ethernet
Serial
100BASE-FX (ST connector)
Glass fiber (ST connector)
EIA-485
IEC 61850–8–1
●
-
-
DNP3
●
●
●
IEC 60870-5-103
-
●
●
●
= Supported
When double Ethernet ports are activated, make sure that the two ports are
connected to different subnets. For example: Port 1 has IP-address 138.227.102.10
with subnet mask 255.255.255.0 and port 2 has IP-address 138.227.103.10 with
subnet mask 255.255.255.0
18.4.3
Settings
PID-6495-SETTINGS v3
Table 810: IEC61850-8-1 Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disabled/Enabled
PortSelGOOSE
Front
LANAB
LANCD
-
-
LANAB
Port selection for GOOSE communication
PortSelMMS
Front
LANAB
LANCD
Any
-
-
Any
Port selection for MMS communication
Protocol Edition
Ed 1
Ed 2
-
-
Ed 1
Protocol Edition
RemoteModControl
Disabled
Maintenance
All levels
-
-
Disabled
Remote Mode Control
AllowSimulation
No
Yes
-
-
No
Allow simulated GOOSE values or
simulated sampled measured values
IEC61850BufTimEnable
Disabled
Enabled
-
-
Enabled
Enable BRC buf time behavior
EnableSettings
Disabled
Enabled
-
-
Disabled
Enable 61850 Edition 2 setting
ResvTms
1 - 3600
s
1
60
Reservation time
1MRK 502 066-UUS B
Section 18
Station communication
1115
Technical manual
Содержание Relion 670 series
Страница 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 62: ...56 ...
Страница 182: ...176 ...
Страница 692: ...686 ...
Страница 726: ...720 ...
Страница 1014: ...1008 ...
Страница 1242: ...1236 ...
Страница 1362: ...1356 ...
Страница 1386: ...1380 ...
Страница 1422: ...1416 ...
Страница 1431: ...1425 ...