Figure 14:
Proposed test points for phase-to-phase loop of circular characteristic in solidly
earthed system
Table 16:
Test points for phase-to-phase loop of circular characteristic in solidly earthed system
Test point
R
X
Comment
P1
Z1CircleStart
∗
cos(
LineAng
)
Z1CircleStart
∗
sin(
LineAng
)
P2
0.8
∗
Z1CircleStart
∗
cos(
ArgLd
)
0.8
∗
Z1CircleStart
∗
sin(
ArgLd
)
P3
RLd
0
P4
-
Z1CircleStart
∗
cos(
LineAng
)
-
Z1CircleStart
∗
sin(
LineAng
)
P5
-0.8
∗
Z1CircleStart
∗
cos(
ArgLd
)
-0.8
∗
Z1CircleStart
∗
sin(
ArgLd
)
P6
-RLd
0
P7
Z1CircleStart
∗
cos(
ArgLd
)
-
Z1CircleStart
∗
sin(
ArgLd
)
P8
-
Z1CircleStart
∗
cos(
ArgLd
)
Z1CircleStart
∗
sin(
ArgLd
)
1.
Change the magnitude and angle of phase-to-phase voltage to achieve impedances at test
points P1, P2, …, P8.
2.
For each test point, observe that the output signals STELEMST, STNDZL1 and STNDZL2 are
activated.
Section 10
1MRK 506 377-UEN Rev. K
Testing functionality by secondary injection
76
Railway application RER670
Commissioning manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Содержание Relion 670 series
Страница 1: ...Relion 670 SERIES Railway application RER670 Version 2 2 IEC Commissioning manual...
Страница 2: ......
Страница 22: ...16...
Страница 26: ...20...
Страница 38: ...32...
Страница 48: ...42...
Страница 54: ...48...
Страница 58: ...52...
Страница 72: ...66...
Страница 178: ...172...
Страница 186: ...180...
Страница 187: ...181...