The sum of the numbers in column “Value when activated” when all INx (where 1≤x≤16) are
active that is=1; is 65535. 65535 is the highest boolean value that can be converted to an
integer by the B16I function block.
16.9
Boolean to integer conversion with logical node
representation, 16 bit BTIGAPC
SEMOD175753-1 v4
16.9.1
Identification
SEMOD175757-2 v5
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Boolean to integer conversion with
logical node representation, 16 bit
BTIGAPC
-
-
16.9.2
Application
SEMOD175849-4 v5
Boolean 16 to integer conversion with logic node representation function BTIGAPC is used to
transform a set of 16 binary (logical) signals into an integer. BTIGAPC can receive an integer
from a station computer – for example, over IEC 61850–8–1. These functions are very useful
when you want to generate logical commands (for selector switches or voltage controllers) by
inputting an integer number. BTIGAPC has a logical node mapping in IEC 61850.
The Boolean 16 to integer conversion function (BTIGAPC) will transfer a combination of up to
16 binary inputs INx where 1≤x≤16 to an integer. Each INx represents a value according to the
table below from 0 to 32768. This follows the general formula: INx = 2
x-1
where 1≤x≤16. The sum
of all the values on the activated INx will be available on the output OUT as a sum of the values
of all the inputs INx that are activated. OUT is an integer. When all INx where 1≤x≤16 are
activated that is = Boolean 1 it corresponds to that integer 65535 is available on the output
OUT. BTIGAPC function is designed for receiving up to 16 booleans input locally. If the BLOCK
input is activated, it will freeze the output at the last value.
Values of each of the different OUTx from function block BTIGAPC for 1≤x≤16.
The sum of the value on each INx corresponds to the integer presented on the output OUT on
the function block BTIGAPC.
Name of input
Type
Default
Description
Value when
activated
Value when
deactivated
IN1
BOOLEAN
0
Input 1
1
0
IN2
BOOLEAN
0
Input 2
2
0
IN3
BOOLEAN
0
Input 3
4
0
IN4
BOOLEAN
0
Input 4
8
0
IN5
BOOLEAN
0
Input 5
16
0
IN6
BOOLEAN
0
Input 6
32
0
IN7
BOOLEAN
0
Input 7
64
0
IN8
BOOLEAN
0
Input 8
128
0
IN9
BOOLEAN
0
Input 9
256
0
IN10
BOOLEAN
0
Input 10
512
0
IN11
BOOLEAN
0
Input 11
1024
0
Table continues on next page
1MRK 505 343-UEN B
Section 16
Logic
643
Application manual
Содержание Relion 670 series
Страница 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 1 IEC Application manual...
Страница 2: ......
Страница 40: ...34...
Страница 64: ...58...
Страница 150: ...144...
Страница 406: ...400...
Страница 472: ...466...
Страница 494: ...488...
Страница 512: ...506...
Страница 524: ...518...
Страница 604: ...598...
Страница 686: ...680...
Страница 718: ...712...
Страница 722: ...716...
Страница 758: ...752...
Страница 759: ...753...