IEC08000479 V2 EN
Figure 293:
TRM connection diagram
21.2.5.3
Technical data
Table 641:
TRM - Energizing quantities, rated values and limits for protection transformer modules
Quantity
Rated value
Nominal range
Current
I
n
= 1 or 5 A
(0.2-40) × I
n
Operative range
(0-100) x I
n
Permissive overload
4 × I
n
cont.
100 × I
n
for 1 s
*)
Burden
< 150 mVA at I
n
= 5 A
< 20 mVA at I
n
= 1 A
Ac voltage
V
n
= 120 V
0.5–288 V
Operative range
(0–340) V
Permissive overload
420 V cont.
450 V 10 s
Table continues on next page
1MRK 511 365-UUS A
Section 21
IED hardware
Phasor measurement unit RES670 2.1 ANSI
763
Technical manual