Name
Type
Description
OUT14
BOOLEAN
Single command output 14
OUT15
BOOLEAN
Single command output 15
OUT16
BOOLEAN
Single command output 16
14.6.5
Settings
Table 251:
SINGLECMD Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Steady
Pulsed
-
-
Disabled
Operation Disabled/Enabled
14.6.6
Operation principle
Single command, 16 signals (SINGLECMD) function has 16 binary output signals. The
outputs can be individually controlled from a substation automation system or from the
local HMI. Each output signal can be given a name with a maximum of 13 characters in
PCM600.
The output signals can be of the types Disabled, Steady, or Pulse. This configuration
setting is done via the local HMI or PCM600 and is common for the whole function block.
The length of the output pulses are 100 ms. In steady mode, SINGLECMD function has
a memory to remember the output values at power interruption of the IED. Also a BLOCK
input is available used to block the updating of the outputs.
The output signals, OUT1 to OUT16, are available for configuration to built-in functions
or via the configuration logic circuits to the binary outputs of the IED.
1MRK 511 365-UUS A
Section 14
Control
Phasor measurement unit RES670 2.1 ANSI
409
Technical manual
Содержание Relion 670 Series RES670
Страница 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 36: ...30 ...
Страница 76: ...70 ...
Страница 106: ...100 ...
Страница 150: ...144 ...
Страница 274: ...268 ...
Страница 326: ...320 ...
Страница 356: ...350 ...
Страница 382: ...376 ...
Страница 416: ...410 ...
Страница 590: ...584 ...
Страница 604: ...598 ...
Страница 694: ...688 ...
Страница 756: ...750 ...
Страница 834: ...828 ...
Страница 836: ...830 ...
Страница 876: ...870 ...
Страница 886: ...880 ...
Страница 887: ...881 ...