8.7.4
Signals
Table 141:
GOPPDOP (32) Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Current group connection
V3P
GROUP
SIGNAL
-
Voltage group connection
BLOCK
BOOLEAN
0
Block of function
BLOCK1
BOOLEAN
0
Block of stage 1
BLOCK2
BOOLEAN
0
Block of stage 2
Table 142:
GOPPDOP (32) Output signals
Name
Type
Description
TRIP
BOOLEAN
Common trip signal
TRIP1
BOOLEAN
Trip of stage 1
TRIP2
BOOLEAN
Trip of stage 2
PICKUP
BOOLEAN
Common pickup
PICKUP1
BOOLEAN
Pickup of stage 1
PICKUP2
BOOLEAN
Pickup of stage 2
P
REAL
Active power P in MW
PPERCENT
REAL
Active power P in % of SBase
Q
REAL
Reactive power Q in MVAr
QPERCENT
REAL
Reactive power Q in % of SBase
8.7.5
Settings
Table 143:
GOPPDOP (32) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disabled/Enabled
OpMode1
Disabled
OverPower
-
-
OverPower
Operation mode for stage 1 Off / On
Power1
0.0 - 500.0
%SB
0.1
120.0
Stage 1 overpower setting in Angle1 direction
in % of SBase
Angle1
-180.0 - 180.0
Deg
0.1
0.0
Characteristic angle for max power senistivity
stage 1
TripDelay1
0.01 - 6000.00
s
0.01
1.00
Trip delay for stage 1
DropDelay1
0.01 - 6000.00
s
0.01
0.06
Drop-off delay for stage 1
Table continues on next page
Section 8
1MRK 511 365-UUS A
Current protection
260
Phasor measurement unit RES670 2.1 ANSI
Technical manual
Содержание Relion 670 Series RES670
Страница 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 36: ...30 ...
Страница 76: ...70 ...
Страница 106: ...100 ...
Страница 150: ...144 ...
Страница 274: ...268 ...
Страница 326: ...320 ...
Страница 356: ...350 ...
Страница 382: ...376 ...
Страница 416: ...410 ...
Страница 590: ...584 ...
Страница 604: ...598 ...
Страница 694: ...688 ...
Страница 756: ...750 ...
Страница 834: ...828 ...
Страница 836: ...830 ...
Страница 876: ...870 ...
Страница 886: ...880 ...
Страница 887: ...881 ...