
The function can be totally blocked by activating the input BLOCK. Tripping can
be blocked by activating the input BLKTR. Signal send can be blocked by
activating the input BLKCS.
12.1.6.4
Permissive overreaching scheme
M13893-22 v6
In a permissive overreaching scheme, a forward directed overreaching measuring
element (normally zone2) sends a permissive signal CS to the remote end if a fault
is detected in forward direction. The received signal CR is used to allow an
overreaching zone to trip after the settable
tCoord
timer has elapsed. The
tCoord
in
permissive overreaching schemes is normally set to zero.
The logic for trip signal in permissive scheme is shown in figure
CACC
CR
tCoord
TRIP
AND
t
en05000513.vsd
IEC05000513 V1 EN-US
Figure 220:
Logic for trip signal in permissive scheme
The function can be totally blocked by activating the input BLOCK. Tripping can
be blocked by activating the input BLKTR. Signal send can be blocked by
activating the input BLKCS.e.
12.1.6.5
Unblocking scheme
M13893-31 v8
In unblocking scheme, the lower dependability of a permissive scheme is overcome
by using the loss of guard signal from the communication equipment to locally
create a receive signal. It is common or suitable to use the function when older, less
reliable power-line carrier (PLC) communication is used.
The unblocking function uses a guard signal CRG, which must always be present,
even when no CR signal is received. The absence of the CRG signal for a time
longer than the setting
tSecurity
time is used as a CR signal, see figure
enables a permissive scheme to operate when the line fault blocks the signal
transmission. The CRG signal is only used in unblocking schemes.
The received signal created by the unblocking function is reset 150 ms after the
security timer has elapsed. When that occurs an output signal LCG is activated for
signalling purpose. The unblocking function is reset 200 ms after that the guard
signal is present again.
Section 12
1MRK 506 382-UEN A
Scheme communication
438
Line distance protection REL650 2.2 IEC
Technical manual
Содержание RELION 650 SERIES
Страница 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Страница 2: ......
Страница 46: ...40 ...
Страница 56: ...50 ...
Страница 164: ...158 ...
Страница 264: ...258 ...
Страница 304: ...298 ...
Страница 320: ...314 ...
Страница 338: ...332 ...
Страница 438: ...432 ...
Страница 468: ...462 ...
Страница 534: ...528 ...
Страница 646: ...640 ...
Страница 660: ...654 ...
Страница 676: ...670 ...
Страница 800: ...794 ...
Страница 836: ...830 ...
Страница 890: ...884 ...
Страница 894: ...888 ...
Страница 940: ...934 ...
Страница 941: ...935 ...