11.1.5
Settings
PID-6724-SETTINGS v2
Table 190:
SESRSYN Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
OperationSynch
Off
On
-
-
Off
Operation for synchronizing function
Off/On
UHighBusSynch
50.0 - 120.0
%UBB
1.0
80.0
Voltage high limit bus for synchronizing
in % of UBaseBus
UHighLineSynch
50.0 - 120.0
%UBL
1.0
80.0
Voltage high limit line for synchronizing
in % of UBaseLine
UDiffSynch
0.02 - 0.50
pu
0.01
0.10
Voltage difference limit for synchronizing
in p.u of set voltage base value
FreqDiffMin
0.003 - 0.250
Hz
0.001
0.010
Minimum frequency difference limit for
synchronizing
FreqDiffMax
0.050 - 1.000
Hz
0.001
0.200
Maximum frequency difference limit for
synchronizing
CloseAngleMax
15.0 - 30.0
Deg
1.0
15.0
Maximum closing angle between bus
and line for synchronizing
FreqRateChange
0.000 - 0.500
Hz/s
0.001
0.300
Maximum allowed frequency rate of
change
tBreaker
0.000 - 1.000
s
0.001
0.080
Closing time of the breaker
tClosePulse
0.050 - 60.000
s
0.001
0.200
Breaker closing pulse duration
tMaxSynch
0.00 - 6000.00
s
0.01
600.00
Resets synch if no close has been made
before set time
tMinSynch
0.000 - 60.000
s
0.001
2.000
Minimum time to accept synchronizing
conditions
OperationSC
Off
On
-
-
On
Operation for synchronism check
function Off/On
UHighBusSC
50.0 - 120.0
%UBB
1.0
80.0
Voltage high limit bus for synchrocheck
in % of UBaseBus
UHighLineSC
50.0 - 120.0
%UBL
1.0
80.0
Voltage high limit line for synchrocheck
in % of UBaseLine
UDiffSC
0.02 - 0.50
pu
0.01
0.15
Voltage difference limit for synchrocheck
in p.u of set voltage base value
FreqDiffA
0.003 - 1.000
Hz
0.001
0.010
Frequency difference limit between bus
and line Auto
FreqDiffM
0.003 - 1.000
Hz
0.001
0.010
Frequency difference limit between bus
and line Manual
PhaseDiffA
5.0 - 90.0
Deg
1.0
25.0
Phase angle difference limit between
bus and line Auto
PhaseDiffM
5.0 - 90.0
Deg
1.0
25.0
Phase angle difference limit between
bus and line Manual
tSCA
0.000 - 60.000
s
0.001
0.100
Time delay output for synchrocheck Auto
tSCM
0.000 - 60.000
s
0.001
0.100
Time delay output for synchrocheck
Manual
Table continues on next page
1MRK 506 382-UEN A
Section 11
Control
Line distance protection REL650 2.2 IEC
337
Technical manual
Содержание RELION 650 SERIES
Страница 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Страница 2: ......
Страница 46: ...40 ...
Страница 56: ...50 ...
Страница 164: ...158 ...
Страница 264: ...258 ...
Страница 304: ...298 ...
Страница 320: ...314 ...
Страница 338: ...332 ...
Страница 438: ...432 ...
Страница 468: ...462 ...
Страница 534: ...528 ...
Страница 646: ...640 ...
Страница 660: ...654 ...
Страница 676: ...670 ...
Страница 800: ...794 ...
Страница 836: ...830 ...
Страница 890: ...884 ...
Страница 894: ...888 ...
Страница 940: ...934 ...
Страница 941: ...935 ...