R
CT
The secondary resistance of the CT (
W
)
R
L
The resistance of the secondary cable and additional load (
W
). The loop
resistance containing the phase and neutral wires, must be used for faults
in solidly grounded systems. The resistance of a single secondary wire
should be used for faults in high impedance grounded systems.
S
R
The burden of an IED current input channel (VA). S
R
=0.010 VA/channel for
I
r
=1 A and S
R
=0.250 VA/channel for I
r
=5 A
Independent of the value of I
op
the maximum required E
al
is specified according to the following:
s n
R
a l
a lre q ma x
CT
L
2
pn
n
k ma x
I
S
E
E
I
R
R
I
I
³
=
×
+
+
æ
ö
×
ç
÷
è
ø
EQUATION1680 V1 EN-US
(Equation 35)
where
I
kmax
Maximum primary fundamental frequency current for close-in faults (A)
16.1.6.5
Directional phase and residual overcurrent protection
M11624-3 v5
If the directional overcurrent function is used the CTs must have a rated equivalent secondary
e.m.f. E
al
that is larger than or equal to the required equivalent secondary e.m.f. E
alreq
below:
s n
R
a l
a lre q
CT
L
2
pn
n
k ma x
I
S
E
E
I
R
R
I
I
³
=
×
+
+
æ
ö
×
ç
÷
è
ø
EQUATION1681 V1 EN-US
(Equation 36)
where:
I
kmax
Maximum primary fundamental frequency current for close-in forward and reverse faults (A)
I
pn
The rated primary CT current (A)
I
sn
The rated secondary CT current (A)
I
n
The rated current of the protection IED (A)
R
CT
The secondary resistance of the CT (
W
)
R
L
The resistance of the secondary cable and additional load (
W
). The loop resistance containing the phase
and neutral wires, must be used for faults in solidly grounded systems. The resistance of a single
secondary wire should be used for faults in high impedance grounded systems.
S
R
The burden of an IED current input channel (VA). S
r
=0.010 VA/channel for I
r
=1 A and S
r
=0.250 VA/channel
for I
r
=5 A
Section 16
1MRK 505 287-UUS B
Requirements
244
Busbar protection REB650
Application manual
© Copyright 2013 ABB. All rights reserved
Содержание RELION 650 SERIES
Страница 1: ...Relion 650 SERIES Busbar protection REB650 Version 1 3 ANSI Application manual...
Страница 2: ......
Страница 22: ...16...
Страница 34: ...28...
Страница 56: ...50...
Страница 64: ...58...
Страница 76: ...70...
Страница 120: ...114...
Страница 184: ...178...
Страница 216: ...210...
Страница 220: ...214...
Страница 254: ...248...
Страница 261: ...255...