Check the IEC61850 and DNP3 communication status in internal event list in
Main menu/Diagnostics/IED Status/General
.
•
In case of persistent faults originating from IED's internal faults such as
component breakdown, contact ABB for repair or replacement actions.
8.1.3.1
Checking the communication link operation
There are several different communication links on the product. First check that all
communication ports that are used for communication are turned on.
1.
Check the front communication port RJ-45.
1.1. Check that the uplink LED is lit with a steady green light.
The uplink LED is located on the LHMI above the RJ-45 communication
port on the left. The port is used for direct electrical communication to a PC
connected via a crossed-over Ethernet cable.
1.2. Check the communication status of the front port via the LHMI in
Main
menu/Test/Function status/Communication/1:DOSFRNT/Outputs
.
Check that the
LINKUP
value is 1, that is, the communication is working.
When the value is 0, there is no communication link.
The rear port connector X0 is used for connecting an external
HMI to the IED. If the
LINKUP
value is 0 for front port, there is
no communication link via port X0. Do not use rear port
connector X0 if the IED is equipped with an LHMI.
2.
Check the communication status of the rear port X1 via the LHMI in
Main menu/
Test/Function status/Communication/1:DOSLAN1/Outputs
.
The X1 communication port on the rear side of the IED is for optical Ethernet via
LC connector or electrical via RJ-45 connector of the IEC 61850-8-1 station bus
communication.
•
Check that the
LINKUP
value is 1, that is, the communication is working.
When the value is 0, there is no communication link.
8.1.3.2
Checking the time synchronization
•
Select
Main menu/Diagnostics/IED status/General
and check the status of the
time synchronization on
Time Synch
.
The
Time synch
value is
Normal
when the synchronization is in order.
Section 8
1MRK 506 331-UUS A
Troubleshooting
150
Commissioning Manual