Name
Values (Range)
Unit
Step
Default
Description
URepTyp
Cyclic
Dead band
Int deadband
-
-
Dead band
Reporting type
ULimHys
0.000 - 100.000
V
0.001
5.000
Hysteresis value in % of range and is
common for all limits
UAngDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
Table 260:
VNMMXU Non group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
UZeroDb
0 - 100000
m%
1
500
Zero point clamping in 0,001% of range
UHiHiLim
0 - 2000000
V
1
96000
High High limit (physical value)
UHiLim
0 - 2000000
V
1
86000
High limit (physical value)
ULowLim
0 - 2000000
V
1
71000
Low limit (physical value)
ULowLowLim
0 - 2000000
V
1
66000
Low Low limit (physical value)
UMin
0 - 2000000
V
1
0
Minimum value
12.1.7.5
Monitored data
Table 261:
VNMMXU Monitored data
Name
Type
Values (Range)
Unit
Description
UL1
REAL
-
kV
UL1 Amplitude,
magnitude of reported
value
UL1ANGL
REAL
-
deg
UL1 Angle, magnitude of
reported value
UL2
REAL
-
kV
UL2 Amplitude,
magnitude of reported
value
UL2ANGL
REAL
-
deg
UL2 Angle, magnitude of
reported value
UL3
REAL
-
kV
UL3 Amplitude,
magnitude of reported
value
UL3ANGL
REAL
-
deg
UL3 Angle, magnitude of
reported value
12.1.8
Operation principle
12.1.8.1
Measurement supervision
The protection, control, and monitoring IEDs have functionality to measure and
further process information for currents and voltages obtained from the pre-
1MRK 505 288-UEN A
Section 12
Monitoring
329
Technical manual
Содержание Relion 650 Series REB650
Страница 1: ...Relion 650 series Busbar protection REB650 Technical manual ...
Страница 2: ......
Страница 36: ...30 ...
Страница 44: ...38 ...
Страница 58: ...52 ...
Страница 80: ...74 ...
Страница 84: ...78 ...
Страница 152: ...146 ...
Страница 278: ...272 ...
Страница 316: ...310 ...
Страница 432: ...426 ...
Страница 504: ...498 ...
Страница 518: ...512 ...
Страница 566: ...560 ...
Страница 567: ...561 ...