
GUID-5C185EAC-13D0-40BD-8511-58CA53EFF7DE V1 EN-US
Figure 12:
A 25.5 mm
B 220 mm
C 13 mm
D 265.9 mm
E 258.6 mm
F 265.9 mm
G 224 mm
Check the allowed minimum bending radius from the optical cable
manufacturer.
5.3.5
Arranging ventilation
GUID-9E1949A6-180D-4626-9784-C06A9A65FE89 v1
Ventholes are located at the bottom and on the back plate of the IED. Reserve sufficient space
round the IED to ensure adequate ventilation.
•
Reserve at least 1U below and above the unit.
•
Reserve for rack mount approximately 10 cm behind the unit, measured from the surface
of the cover.
•
Ensure sufficient space for the wiring and the installation of cable ducts.
1MRK 514 014-UEN A
Section 5
Mounting
650 series
27
Installation manual
© Copyright 2011 ABB. All rights reserved