Table 25:
SMAI_20_1 Output signals
Name
Type
Description
SPFCOUT
REAL
Number of samples per fundamental cycle from
internal DFT reference function
AI3P
GROUP SIGNAL
Grouped three phase signal containing data from
inputs 1-4
AI1
GROUP SIGNAL
Quantity connected to the first analog input
AI2
GROUP SIGNAL
Quantity connected to the second analog input
AI3
GROUP SIGNAL
Quantity connected to the third analog input
AI4
GROUP SIGNAL
Quantity connected to the fourth analog input
AIN
GROUP SIGNAL
Calculated residual quantity if inputs 1-3 are
connected
3.8.2.3
Settings
Only values 1-3 of the parameter
GlobalBaseSel
should normally be
used. The values 1-3 refer to the global base value groups Phase Grp
1, Phase Grp 2 and Phase Grp 3 correspondingly (BASEPH1,
BASEPH2 and BASEPH3 in PCM600). The selection affects the
actual limit for frequency calculation set by
MinValFreqMeas
which
by default is 10% of the
Voltage base Val PP
in the selected group.
The values 4-6 refer to Residual Grp 1, Residual Grp 2 and Residual
Grp 3 (BASERES1, BASERES2 and BASERES3 in PCM600)
correspondingly and they are typically not to be used in this
connection.
Section 3
1MRS757256 F
Basic functions
58
PML630/Compact Load-Shedding Solution
Technical Manual