![ABB Relion 630 Series Скачать руководство пользователя страница 48](http://html.mh-extra.com/html/abb/relion-630-series/relion-630-series_technical-manual_2813048.webp)
Activating
signal RED
LED
Acknow.
IEC09000315-1-en.vsd
Activating
signal YELLOW
G
G
R
R
Y
Activating
signal GREEN
IEC09000315 V1 EN
Figure 18:
Operating sequence 3, three colors involved, alternative 2
Sequence 4 (LatchedAck-S-F)
This sequence has the same functionality as sequence 3, but steady and flashing light
have been alternated.
Sequence 5 (LatchedColl-S)
This sequence has a latched function and works in collecting mode. At the activation
of the input signal, the indication lights up with a steady light. The difference to
sequence 3 and 4 is that the indications that are still activated are not affected by the
reset, that is, immediately after the positive edge of the reset is executed, a new reading
and storing of active signals is performed. Every LED is independent of the other
LEDs in its operation.
IEC01000235_2_en.vsd
Activating
signal
LED
Reset
IEC01000235 V2 EN
Figure 19:
Operating sequence 5 (LatchedColl-S)
That means if an indication with higher priority has reset while an indication with
lower priority still is active at the time of reset, the LED changes color according to
Section 3
1MRS757256 F
Basic functions
42
PML630/Compact Load-Shedding Solution
Technical Manual