7.4.6
Settings
Table 273:
PSCSWI Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Start value
0.05 - 5.00
pu
0.01
0.05
Start value
Start value Mult
0.8 - 10.0
-
0.1
1.0
Multiplier for scaling the start value
Time multiplier
0.05 - 15.00
-
0.05
1.00
Time multiplier in IEC/ANSI curves
Operating curve type
ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Programmable
RI type
RD type
-
-
IEC Def. Time
Selection of time delay curve type
Operate delay time
0.04 - 200.00
s
0.01
0.04
Operate delay time
Table 274:
PSCSWI Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
Type of reset curve
Immediate
Def time reset
Inverse reset
-
-
Immediate
Selection of reset curve type
Table 275:
PSCSWI Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Block override
No
IED test mode
Quality bad CB
close
Quality bad CB
open
CB Interm or invalid
All yes
-
-
No
Bypass block due to IED test or data
quality or CB position
Maximum Ava power
0.0 - 999999.9
kW
0.1
0.0
Maximum available power of power
source
Governor mode
Droop
MW
ISO
P-Control
Optimize
Base load
Peak load
-
-
ISO
Governor mode of generator
Table continues on next page
1MRS757256 F
Section 7
Power management functions
PML630/Compact Load-Shedding Solution
231
Technical Manual
Содержание Relion 630 Series
Страница 1: ... RELION 630 SERIES Power Management PML630 Compact Load Shedding Solution Technical Manual ...
Страница 2: ......
Страница 26: ...20 ...
Страница 38: ...32 ...
Страница 202: ...196 ...
Страница 322: ...316 ...
Страница 360: ...354 ...
Страница 374: ...368 ...
Страница 376: ...370 ...