Table 244:
SPVNZBAT Output signals
Name
Type
Description
AL_ULOW
BOOLEAN
Alarm when voltage has been below lower limit for
a set time
AL_UHIGH
BOOLEAN
Alarm when voltage has exceeded higher limit for a
set time
ST_ULOW
BOOLEAN
Start signal when battery voltage drops below
lower limit
ST_UHIGH
BOOLEAN
Start signal when battery voltage exceeds upper
limit
5.1.7
Settings
Table 245:
SPVNZBAT Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
On
Operation Off/On
Battery voltage Rtg
20.00 - 250.00
V
1.00
110.00
Battery rated voltage
Low battery value
0.60 - 1.40
pu
0.01
0.70
Lower limit for the battery terminal voltage
High battery value
0.60 - 1.40
pu
0.01
1.20
Upper limit for the battery terminal voltage
Alarm delay time
0.100 - 60.000
s
0.001
0.200
Delay time for alarm
Table 246:
SPVNZBAT Non group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
Reset delay time
0.000 - 60.000
s
0.001
0.000
Reset time provided to reset the timers
5.1.8
Measured values
Table 247:
SPVNZBAT Measured values
Name
Type
Default
Description
U_BATT_IN
REAL
0.00
Battery terminal voltage
BLOCK
BOOLEAN
0
Block of function
BLK_AL
BOOLEAN
0
Blocks the alarm signals
BLK_ST
BOOLEAN
0
Blocks the start signals
Section 5
1MRS757256 F
Supervision functions
194
PML630/Compact Load-Shedding Solution
Technical Manual