3.31.3
Operation principle
Upon receiving the input signals, the IEC 61850 generic communication I/O functions
(DPGGIO) function block sends the signals over IEC 61850-8-1 to the equipment or
system that requests these signals. To be able to get the signals, PCM600 must be used
to define which function block in which equipment or system should receive this
information.
3.31.4
Signals
Table 113:
DPGGIO Input signals
Name
Type
Default
Description
OPEN
BOOLEAN
0
Open indication
CLOSE
BOOLEAN
0
Close indication
VALID
BOOLEAN
0
Valid indication
Table 114:
DPGGIO Output signals
Name
Type
Description
POSITION
INTEGER
Double point indication
3.31.5
Settings
The function does not have any parameters available in LHMI or PCM600.
3.32
Configurable logic blocks
3.32.1
Standard configurable logic blocks
A number of logic blocks and timers are available to be used to adapt the configuration
to the specific application needs.
•
OR
•
INVERTER
inverts the input signal
•
PULSETIMER
can be used, for example, for pulse extensions or limiting of
operation of outputs
•
GATE
is used for controlling if a signal should be able to pass from the input to
the output or not, depending on a setting
Section 3
1MRS757256 F
Basic functions
140
PML630/Compact Load-Shedding Solution
Technical Manual