Name
Values (Range)
Unit
Step
Default
Description
MV lLim
-5000.00 - 5000.00
xBase
0.01
-800.00
Low limit multiplied with the base prefix
(multiplication factor)
MV llLim
-5000.00 - 5000.00
xBase
0.01
-900.00
Low Low limit multiplied with the base
prefix (multiplication factor)
MV min
-5000.00 - 5000.00
xBase
0.01
-1000.00
Minimum value multiplied with the base
prefix (multiplication factor)
MV max
-5000.00 - 5000.00
xBase
0.01
1000.00
Maximum value multiplied with the base
prefix (multiplication factor)
MV dbType
Cyclic
Dead band
Int deadband
-
-
Dead band
Reporting type
MV limHys
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range (common
for all limits)
3.30.7
Monitored data
Table 112:
MVGGIO Monitored data
Name
Type
Values (Range)
Unit
Description
VALUE
REAL
-
-
Magnitude of deadband
value
RANGE
INTEGER
0=Normal
1=High
2=Low
3=High-High
4=Low-Low
-
Range
3.31
IEC 61850 generic communication I/O functions
DPGGIO
3.31.1
Function block
DPGGIO
OPEN
CLOSE
VALID
POSITION
IEC09000075_1_en.vsd
IEC09000075 V1 EN
Figure 73:
Function block
3.31.2
Functionality
The IEC 61850 generic communication I/O functions (DPGGIO) function block is
used to send double indications to other systems or equipment in the substation. It is
especially used in the interlocking and reservation station-wide logics.
1MRS757256 F
Section 3
Basic functions
PML630/Compact Load-Shedding Solution
139
Technical Manual