![ABB Relion 630 Series Скачать руководство пользователя страница 143](http://html1.mh-extra.com/html/abb/relion-630-series/relion-630-series_engineering-manual_3428217143.webp)
Section 10
Configuration migration
10.1
Migrating the configuration to a later version
PCM600 Ver.2.5 or later and 630 series Connectivity Package Ver.1.3 support
migration from 630 series Ver.1.0 to Ver.1.1, Ver.1.1 to Ver.1.2 and Ver.1.2 to Ver.
1.3. However, due to changes in the functions, reengineering is necessary.
•
Make sure that the new function versions in the updated product fulfil the
requirements.
•
Be careful when replacing functions, signals or parameters that were removed at
migration.
The actual migration is done by IED Configuration Migration in PCM600. Updating
the complete configuration requires updates in the tools too, such as Application
Configuration tool, Parameter Setting tool and Graphical Display Editor.
10.1.1
Creating a backup
Since the migration process is not reversible, export a copy of the project for backup.
1.
Select
Open/Manage project
.
2.
Select the project to be exported and click
Export Project
.
10.1.2
Creating a reference IED project
At migration, some functions, signals and parameters are removed, and they have to
be reengineered. Having an original IED object as a reference helps in reengineering.
Create a PDF file of the original Application Configuration tool configuration for easy
comparision.
1.
Create a new IED Group to the PCM600 project.
2.
Copy the original IED object and paste it to created IED Group.
3.
Rename the reference IED object to identify it easily when tools are open for
both IEDs.
The reference IED object can be used while reengineering the IED
configuration. All PCM600 tools can be opened to separate tabs for both the
migrated and the reference IED.
1MRS756800 F
Section 10
Configuration migration
630 series
137
Engineering Manual