Section 8
IEC 60870-5-103 communication
engineering
8.1
Engineering in PCM600
Application Configuration and Parameter Setting in PCM600 are used to configure
the communication for IEC 60870-5-103 protocol.
1.
Add the desired IEC 60870-5-103 function blocks to the application
configuration in the Application Configuration tool.
2.
Connect the outputs of desired protection and monitoring function in the
application configuration to the inputs of the corresponding IEC 60870-5-103
function block.
3.
Set the function type and desired information number, where an information
number must be supplied, for each IEC 60870-5-103 function block instance in
the Parameter Setting tool.
4.
Set the general communication parameters for IEC 60870-5-103 and time
synchronization parameters in the Parameter Setting tool.
See the IEC 60870-5-103 communication protocol manual for more information
about the IEC 60870-5-103 implementation.
1MRS756800 F
Section 8
IEC 60870-5-103 communication engineering
630 series
127
Engineering Manual