IEC 61850 name
SA name
Description
Values
.OpNumAlm.stVal
OPR_ALM
CB operations alarm
1=Alarm
.OpNumLO.stVal
OPR_LO
CB operations lockout
1=Lockout
.PresAlm.stVal
PRES_ALM
Low pressure alarm
1=Alarm
.PresLO.stVal
PRES_LO
Low pressure lockout
1=Lockout
.SprChaAlm.stVal
SPR_CHR_ALM
Spring charge time alarm
1=Alarm
2.3.3.2
LD0.TCSSCBR1 Trip circuit supervision (1)
Table 11:
LD0.TCSSCBR1 Trip circuit supervision (1)
IEC 61850 name
SA name
Description
Values
LD0.TCSSCBR1
.CirAlm.stVal
ALARM
Supervision alarm
1=Alarm
2.3.3.3
LD0.TCSSCBR2 Trip circuit supervision (2)
Table 12:
LD0.TCSSCBR2 Trip circuit supervision (2)
IEC 61850 name
SA name
Description
Values
LD0.TCSSCBR2
.CirAlm.stVal
ALARM
Supervision alarm
1=Alarm
2.3.3.4
LD0.BSTGGIO1 Binary signal transfer supervision
Table 13:
LD0.BSTGGIO1 Binary signal transfer supervision
IEC 61850 name
SA name
Description
Values
LD0.BSTGGIO1
.Alm1.stVal
SEND_SIG_A
Send alarm
1=Alarm
.Alm2.stVal
RECV_SIG_A
Receive alarm
1=Alarm
2.3.4
Metering and measurand functions
2.3.4.1
LD0.CMMXU1 Phase currents (1) limit supervision
Table 14:
LD0.CMMXU1 Phase currents (1) limit supervision
IEC 61850 name
SA name
Description
Values
LD0.CMMXU1
.HiAlm.stVal
HIGH_ALARM
High alarm
1=Alarm
.HiWrn.stVal
HIGH_WARN
High warning
1=Warning
.LoAlm.stVal
LOW_ALARM
Low alarm
1=Alarm
.LoWrn.stVal
LOW_WARN
Low warning
1=Warning
Section 2
1MRS756879 D
DNP3 data mappings
16
RED615
Point List Manual