BitA
RegA
IEC 61850 name
SA name
Description
Values
2954
184.10
.Str.phsC
phsC pickup
1=Pickup
2955
184.11
.mcd
2956
184.12
.Op.general
TRIP
General trip
1=Trip
2957
184.13
.mcd
2.3.1.69
LD0.RESCMMXU1 Residual current measurement (1) – IG-1
Table 72:
LD0.RESCMMXU1 Residual current measurement (1) – IG-1
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.RESCMMXU1
2760
172.08
.HiAlm.stVal
HIGH_ALARM
High alarm
1=Alarm
2761
172.09
.mcd
2762
172.10
.HiWrn.stVal
HIGH_WARN
High warning
1=Warning
2763
172.11
.mcd
2.3.1.70
LD0.RESVMMXU1 Residual voltage measurement (1) – VG-1
Table 73:
LD0.RESVMMXU1 Residual voltage measurement (1) – VG-1
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.RESVMMXU1
2764
172.12
.HiAlm.stVal
HIGH_ALARM
High alarm
1=Alarm
2765
172.13
.mcd
2766
172.14
.HiWrn.stVal
HIGH_WARN
High warning
1=Warning
2767
172.15
.mcd
2.3.1.71
LD0.ROVPTOV1 Residual overvoltage protection (1) – 59G-1
Table 74:
LD0.ROVPTOV1 Residual overvoltage protection (1) – 59G-1
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.ROVPTOV1
4014
250.14
.Str.general
PICKUP
General pickup
1=Pickup
4015
250.14
.mcd
4016
251.0
.Op.general
TRIP
General trip
1=Trip
4017
251.1
.mcd
1MAC252756-MB B
Section 2
Modbus data mappings
REM615 ANSI
47
Point List Manual