![ABB Relion 615 series Скачать руководство пользователя страница 52](http://html1.mh-extra.com/html/abb/relion-615-series/relion-615-series_modbus-point-list-manual_3381023052.webp)
2.3.1.66
LD0.PHPTUV2 Three-phase undervoltage protection (2) – 27-2
Table 69:
LD0.PHPTUV2 Three-phase undervoltage protection (2) – 27-2
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.PHPTUV2
4022
251.6
.Str.general
PICKUP
General pickup
1=Pickup
4023
251.7
.mcd
.Str.phsA
phsA pickup
1=Pickup
.mcd
.Str.phsB
phsB pickup
1=Pickup
.mcd
.Str.phsC
phsC pickup
1=Pickup
.mcd
4024
251.8
.Op.general
TRIP
General trip
1=Trip
4025
251.9
.mcd
2.3.1.67
LD0.PREVPTOC1 Phase reversal protection (1) – 46R-1
Table 70:
LD0.PREVPTOC1 Phase reversal protection (1) – 46R-1
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.PREVPTOC1
2926
182.14
.Str.general
PICKUP
Stage pickup
1=Pickup
2927
182.15
.mcd
2928
183.00
.Op.general
TRIP
Stage trip
1=Trip
2929
183.01
.mcd
2.3.1.68
LD0.PSPTUV1 Positive-sequence undervoltage protection (1) – 27PS
Table 71:
LD0.PSPTUV1 Positive-sequence undervoltage protection (1) – 27PS
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.PSPTUV1
2948
184.04
.Str.general
PICKUP
General pickup
1=Pickup
2949
184.05
.mcd
2950
184.06
.Str.phsA
phsA pickup
1=Pickup
2951
184.07
.mcd
2952
184.08
.Str.phsB
phsB pickup
1=Pickup
2953
184.09
.mcd
Table continues on next page
Section 2
1MAC252756-MB B
Modbus data mappings
46
REM615 ANSI