2.3.1.50
LD0.MNSPTOC1 Negative-sequence overcurrent protection for machines
(1) – 46M-1
Table 53:
LD0.MNSPTOC1 Negative-sequence overcurrent protection for machines (1) – 46M-1
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.MNSPTOC1
2904
181.08
.Str.general
PICKUP
Stage pickup
1=Pickup
2905
181.09
.mcd
2906
181.10
.Op.general
TRIP
Stage trip
1=Trip
2907
181.11
.mcd
2.3.1.51
LD0.MNSPTOC2 Negative-sequence overcurrent protection for machines
(2) – 46M-2
Table 54:
LD0.MNSPTOC2 Negative-sequence overcurrent protection for machines (2) – 46M-2
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.MNSPTOC2
2908
181.12
.Str.general
PICKUP
Stage pickup
1=Pickup
2909
181.13
.mcd
2910
181.14
.Op.general
TRIP
Stage trip
1=Trip
2911
181.15
.mcd
2.3.1.52
LD0.MPTTR1 Thermal overload protection for motors (1) – 49M-1
Table 55:
LD0.MPTTR1 Thermal overload protection for motors (1) – 49M-1
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.MPTTR1
2916
182.04
.StrInh.stVal
BLK_RESTART
Block restart
1=Restart
2917
182.05
.mcd
2930
183.02
.AlmThm.general
ALARM
Thermal alarm
1=Alarm
2931
183.03
.mcd
2932
183.04
.Op.general
TRIP
Thermal trip
1=Trip
2933
183.05
.mcd
1MAC252756-MB B
Section 2
Modbus data mappings
REM615 ANSI
39
Point List Manual
Содержание Relion 615 series
Страница 1: ...RELION 615 SERIES Motor Protection and Control REM615 ANSI Modbus Point List Manual...
Страница 2: ......
Страница 14: ...8...