Section 2
Modbus data mappings
2.1
Overview
This document describes the Modbus data points and structures available in the protection
relay. The point lists describe a superset of all data available through the standard
configuration/s including the optional functionalities.
2.2
Supported functions
2.2.1
Supported functions in REM615
Table 2:
Supported functions
Function
IEC 61850
ANSI
A
B
D
E
MA01
MA02
MA04
MA05
Protection
Three-phase non-directional
overcurrent protection, low
stage
PHLPTOC
51P
1
1
1
1
Three-phase non-directional
overcurrent protection, high
stage
PHHPTOC
50P
1
1
1
2
Three-phase non-directional
overcurrent protection,
instantaneous stage
PHIPTOC
50P-3
1
1
1
1
Non-directional ground-fault
protection, low stage
EFLPTOC
51G
1
1
Non-directional ground-fault
protection, high stage
EFHPTOC
50G
1
1
1
2
Directional ground-fault
protection, low stage
DEFLPDEF
67/51N
1
1
1
Residual overvoltage
protection
ROVPTOV
59G
1
59N
1
Three-phase undervoltage
protection
PHPTUV
27
1
1
2
Three-phase overvoltage
protection
PHPTOV
59
2
Table continues on next page
1MAC252756-MB B
Section 2
Modbus data mappings
REM615 ANSI
17
Point List Manual