![ABB Relion 615 series Скачать руководство пользователя страница 107](http://html1.mh-extra.com/html/abb/relion-615-series/relion-615-series_modbus-point-list-manual_3381023107.webp)
2.5
Controls
Table 180:
Explanations of the controls table columns
Column name
Description
0xA
Coil (0X) address for control value.
CS
Control structure and bit within the structure for control value.
IEC 61850 name
Original IED data object identification. Described in the IEC 61850 format as Logical
Device.Logical Node and thereafter .Data Object.Data Attribute. Logical Node is the
same as the application function block name.
SA name
The signal may have a defined label that is visible, for example, in the Application
Configuration tool in PCM600.
Description
Short description of the signal. See the technical manual for more information.
Value
Meaning of the written value.
2.5.1
Reset, acknowledge and trigger points
Table 181:
Reset, acknowledge and trigger points
0xA
CS
IEC 61850 name
SA name
Description
Values
LD0.LLN0
2060
2.00
.LEDRs1.Oper.ctlVal
Reset indications and LEDs
1=Reset
2061
2.01
.LEDRs2.Oper.ctlVal
Reset alarm LEDs
1=Reset
LD0.PEMMXU1
2062
2.02
.RecRs.Oper.ctlVal
Reset power max demands
1=Reset
2063
2.03
< reserved >
2064
2.04
< reserved >
LD0.SSCBR1
2065
2.05
.RsAccAPwr.Oper.ctlVal
Reset CB accum. energy
1=Reset
2066
2.06
.RsCBWear.Oper.ctlVal
Reset CB wear data
1=Reset
DR.RDRE1
2067
2.07
.RcdTrg.Oper.ctlVal
Trig DR recording
1=Trig
2068
2.08
.MemClr.Oper.ctlVal
Clear DR memory
1=Clear
LD0.CMMXU1
2069
2.09
.RecRs.Oper.ctlVal
Reset max current1 demands
1=Reset
LD0.PEMMXU1
2070
2.10
.SupDmdRs.Oper.ctlVal
Reset energy values
1=Reset
LD0.SCCBR1
2071
2.11
.RsTrvTm.Oper.ctlVal
Reset CB travel time
1=Reset
Table continues on next page
1MAC252756-MB B
Section 2
Modbus data mappings
REM615 ANSI
101
Point List Manual