background image

1

2

3

4

5

6

7

8

9

10

11

12

— 

Quick Start Guide

Relion® 615 series

1

Display

Default view can be selected from single line diagram (SLD), measurements and main menu

2

Self-supervision and
protection indicator LEDs

Ready-LED steady: OK, Ready-LED flashing: Internal Relay Fault (IRF), 
Start-LED steady: protection started, Start-LED flashing: protection function blocked, 
Trip-LED: protection operated

3

Programmable LEDs

Can be programmed for alarming and indication with latching and/or flashing features

4

Control Circuit Breaker (CB) Press open/close and confirm by pressing enter. If there is more than one controllable object 

select the object first with navigation buttons. Note: control has to be in Local mode.

5

Escape / Cancel

Used for canceling actions and leaving setting mode without saving the values. 
Returns back to menu.

6

Navigation 

Left = go back, Right = go further, Up = scroll up, Down = scroll down. 
Up/down can also be used when selecting controllable objects like breakers and 
switches in single line diagram.

7

Enter / Select

Entering to parameter setting mode and confirming new values

8

Authorization

If authorization is used you can log in or log out using this button

9

Clear

Clearing events and indications, see next page for further details

10

Menu

Switch views in between the main menu, single line diagram and measurements

11

Local / Remote

Changes the control between Local/Remote

12

Help

View help messages