BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.GNRLLTMS1
.TmChSt1.stVal
Time synch. status
0/1=Down/Up
.mcd
.TmSyn.stVal
IEC 61850-9-2 sync
0...2
.mcd
.TmSrcSt.stVal
Time sync source
0...99
.mcd
LD0.SCHLCCH1
.ChLiv.stVal
CH1LIV
Ethernet channel 1 live
1=Live
.mcd
LD0.SCHLCCH2
.ChLiv.stVal
CH2LIV
Ethernet channel 2 live
1=Live
.mcd
LD0.SCHLCCH3
.ChLiv.stVal
CH3LIV
Ethernet channel 3 live
1=Live
.mcd
LD0.GSELPRT1
.Alm.stVal
GOOSE alarm
1=Alarm
.mcd
2.3.2.3
DR.RDRE1 Disturbance recorder signals
Table 39:
DR.RDRE1 Disturbance recorder signals
BitA
RegA
IEC 61850 name
SA name
Description
Values
DR.RDRE1
.RcdStr.stVal
Recording started
1=Started
.mcd
.RcdDltInd.stVal
Recording deleted
1=Deleted
.mcd
.OvWrRcdInd.stVal
Overwrite of record
1=Overwrite
.mcd
.PerTrgInd.stVal
Periodic triggering
1=Triggered
.mcd
.ManTrgInd.stVal
Manual triggering
1=Triggered
.mcd
1MRS758336 B
Section 2
Modbus data mappings
REU611
27
Point List Manual