2.3.2
Unmapped indications
Unmapped indications are indication data that have no initial Modbus mapping
locations, but can be added to the user-definable Modbus area using the
Communication Management tool in PCM600. If Modbus events are enabled for
these indication signals, the event identification is the user-definable area address.
2.3.2.1
All premapped three-phase protection function stages, start and
operate/phase-dependent objects added
Table 37:
All premapped three-phase protection function stages, start and operate/phase-dependent objects added
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.xxxxxxxx (various)
.Op.phsA
Operate Phase A
1 = Operate
.mcd
.Str.phsA
Start Phase A
1 = Start
.mcd
.Op.phsB
Operate Phase B
1 = Operate
.mcd
.Str.phsB
Start Phase B
1 = Start
.mcd
.Op.phsC
Operate Phase C
1 = Operate
.mcd
.Str.phsC
Start Phase C
1 = Start
.mcd
2.3.2.2
Common data 2
Table 38:
Common data 2
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.LDEV1
.DevFail.stVal
Internal fault
1=Fault
.mcd
.StLstOv.stVal
Internal ind. overflow
1=Overflow
.mcd
.MeasLstOv.stVal
Internal meas. overflow
1=Overflow
.mcd
.ChgFlg.stVal
Configuration changed
1=Changed
.mcd
.FacSet.stVal
Factory settings in use
1=In use
.mcd
Table continues on next page
Section 2
1MRS758336 B
Modbus data mappings
26
REU611
Point List Manual