INSTA LL ATION INSTRUC TIONS
ReliaGear
®
Merchandised lighting panelboards
ReliaGear
®
Merchandised NEMA 1 interiors
These instructions describe
the installation of a ReliaGear
Merchandised interior into a
ReliaGear lighting panelboard
NEMA 1 enclosure. This interior
is only for use in a 43", 49" or 76"
high enclosure of standard width
and depth.
Installation
Use the following procedure to install a ReliaGear
Merchandised interior into a ReliaGear lighting
panelboard enclosure, as illustrated in figure 1.
1. Remove the four (125 A and 225 A panels) or eight
(400 A and 600 A panels) screws securing the shield
to the panelboard interior. Lift off the shield and
set it and the screws aside.
2. Remove the four interior mounting screws from
position A. Reinstall two of them loosely at position
B, retaining the other two.
3. Mount the box to the wall using the four embossed
mounting holes.
4. Hold the interior near its bottom end, then place
the two key-shaped mounting holes at the top end
of the interior over the mounting screws in the box
at position B. Release the bottom of the interior
and allow it to hang in the box. Secure the bottom
end of the interior to the box at position C with the
two remaining screws removed in step 2. Tighten all
the screws.
5. Reattach the shield to the interior with the four
or eight screws removed in step 1.