17.2
Time synchronization
17.2.1
Functionality
The time synchronization source selector is used to select a common source of absolute
time for the IED when it is a part of a protection system. This makes it possible to compare
event and disturbance data between all IEDs in a station automation system.
Micro SCADA OPC server should not be used as a time synchronization
source.
17.2.2
Time synchronization TIMESYNCHGEN
17.2.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Time synchronization
TIMESYNCHGE
N
-
-
17.2.2.2
Settings
Table 574:
TIMESYNCHGEN Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
CoarseSyncSrc
Disabled
SNTP
DNP
IEC60870-5-103
-
-
Disabled
Coarse time synchronization source
FineSyncSource
Disabled
SNTP
IRIG-B
-
-
Disabled
Fine time synchronization source
SyncMaster
Disabled
SNTP-Server
-
-
Disabled
Activate IED as synchronization master
17.2.3
Time synchronization via SNTP
17.2.3.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Time synchronization via SNTP
SNTP
-
-
Section 17
1MRK 506 335-UUS A
Basic IED functions
746
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...