16.6.4
Signals
Table 554:
GOOSEINTRCV Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
Table 555:
GOOSEINTRCV Output signals
Name
Type
Description
INTOUT
INTEGER
Integer output
DATAVALID
BOOLEAN
Data valid for integer output
COMMVALID
BOOLEAN
Communication valid for integer output
TEST
BOOLEAN
Test output
16.6.5
Settings
Table 556:
GOOSEINTRCV Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Off/On
16.6.6
Operation principle
The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total failure
condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
The input of this GOOSE block must be linked in SMT by means of a cross
to receive the integer values.
The implementation for IEC61850 quality data handling is restricted to a
simple level. If quality data validity is GOOD then the DATAVALID
output will be HIGH. If quality data validity is INVALID,
QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA then the
DATAVALID output will be LOW.
Section 16
1MRK 506 335-UUS A
Station communication
728
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...